Legrand, 3 Pole, 1600A, DRAWOUT DMX³-H 2500 ACB

Legrand, 3 Pole, 1600A, DRAWOUT DMX³-H 2500 ACB View larger

Legrand, 3 Pole, 1600A, DRAWOUT DMX³-H 2500 ACB

0287 44

New product

Add to wishlist

Data sheet

ACB TRIP UNITLSI, LSIg
COUNTRY OF ORIGININDIA
ACB FRAME SIZEFRAME-I
ACB BREAKING CAPACITY65kA
ACB POLES3 POLE
ACB PROTECTION TYPEMICROPROCESSOR BASED
ACB RATING1600A

More info

Features of DMX3  - Draw-out Version ACB

  • Range – 630A to 6300A
  • Three Optimum Frame Sizes
  • Breaking Capacities of 50kA, 65kA & 100kA
  • Advanced Self Powered Electronic Protection Units
  • Options for LSI and LSIg Trip Units
  • L :  Ir  – 0.4 to 1 In,  tr – 5 to 30 sec
  • S : Isd – 1.5 to 10 Ir, tsd – 0.1 to 1  sec
  • I  : Ii – 2 to 15 In
  • G : 0.2 to 1 In, tg – 0.1 to 1 sec
  • Options of LCD and Touch Screen Multi Colour Displays
  • Neutral Overload Protection – OFF-50 %-100 %
  • Communication Ready
  • In Built Temperature Protection
  • Rotatable Terminals for Horizontal/Vertical Orientation
  • Fast Operation
  • Options to install various safety interlock
  • Internal Battery for Trip Units
  • Individual fault diagnosis
  • Individual Fault Counter & Historical Trip Record
  • 6 Programmable Digital Relay Contacts with Time Delay Changeover
  • Option to Measure Current, Voltage, Frequency, Power, Energy, Power Factor and internal battery voltage
  • Advanced Functions of Logical Selectivity, Reverse Power, Current Unbalance, Overvoltage, Undervoltage, Voltage Unbalance, Under Frequency, Over Frequency & Phase Reversal